Rudra Shakti Electronics ----------------------------------------------------------------------------------------------

Home | Products | Profile | Instructions | Enquiry

Instructions for Installation and Commissioning
P.F. / KVAR Controller Models PFR 941/PFR 942
INSTALLATION
The Controller rear panel has A,B,M,L input terminals for external electrical signal input.
1)  A & B terminals are to be connected to 2 phases of a 3 phase electrical system.
     M & L terminals are to be connected to CT secondary
2)  In case the CT secondary is connected to other instruments in addition to the Controller.
     a) current coils of other instruments and controller terminal must be connected in series
     b) rated burden of the CT must be sufficiently large to accommodate the burdens imposed
         by all the instruments, terminal, cable etc. connected in the CT secondary circuit.
3)  The CT must be mounted on
     a) the main incomer bus-bar carrying sum total of load and capacitive currents.
     b) the third phase of the system of which other two phases are already connected to A & B
         terminals of the Controller.
4) The rated current of CT secondary and rated signal input current of the Controller must be
     identical i.e. 5 Amps or 1 Amps. (Check the name plate of the controller for CT secondary
    current required)   
5) The Controller rear panel has K1, K2........ stage wise and KC as a common normally open
     potential free output contact terminal. Hence separate supply to coils of the contractors used for
     switching the capacitor banks must be provided through these terminals. Contact configuration
     with potential free separate contact pairs for each stage K1N1, K2N2.......etc. can be
     provided on request.

COMMISSIONING :
1) Confirm the set-up as per the installation instruction.
2) Check the fuse provided on the Controller rear panel.
3) Switch off all the capacitor bank in the entire circuit.
4) Confirm the CT secondary current with a multimeter by connecting it in series with M & L
     terminals of the Controller. It must be at least 5% of its rated value, for proper functioning of 
     the Controller. (CT secondary can also be checked with clip-on type ammeter)
5) 
Set COS Ø = 1.0 and %KVAR = 0
6)  Switch on the capacitor control panel and the controller.
     a)  if the "O/[V" (red) L.E.D. glows and persists, check if the supply voltage os higher than 
          the safe value.
     b) if the "'ERR" (red) L.E.D. glows and persists, check and rectify external wiring for (i) incorrect
         phase sequence, or (ii) incorrect CT polarity, or (iii) absence of input current signal.
     c) The "ERR" function in (b) above is disenabled in presence of two simultaneous system errors.
         Counter-check against this condition is indicated in (d) below.
     d)  As the load is inductive (see 3 above), the P.F. meter should indicate inductive (-ve) reading 
          within estimated limit and the "-" (red) L.E.D. should glow and persists. if not, verify again the 
          external wiring connection as per (6b) above.

OPERATING INSTRUCTIONS :

1. The 'Auto/Man' switch on the panel must be in 'Auto' position.
2. Position of "TEST" push button must be outward.
3. Set the cos Ø
setting to the value calculated from the following formula.
4. Set % KVAR setting to the value calculated from the following formula
          % KVAR = 60 X (KVAR per capacitor stage ) / x V x I (model PFR 941)
                      % KVAR = 100 (minimum / first stage KVAR / x V x I (model PFR 942)
          Where, V = rated capacitor voltage in KV (0.415 KV etc.)
                      I = rated primary current of main incomer CT in Amps.
Note - All capacitor stages should be of equal KVAR rating in Model PFR 941
5. P.F. meter indicates the system p.f. system (-ve sign for inductive p.f.)
6. If the '-' (red) L.E.D. glows and persists, system requires capacitive load. The "switch on " cycle 
    of the capacitor bank stages commences and after some delay, stage L.E.D.s and capacitors
    start switching on sequentially. As the capacitor banks are switched on, the system p. f. starts
    improving from initial low p.f. to 1.0 p.f.
7. If the '+' (amber) L.E.D. glows and persists, systems has more capacitive load than required. The
    " switch off " cycle of the capacitor bank stage commences and after some delay, stage L.E.D.s
    and capacitors start switching off sequentially.
8. Glowing of green L.E.D. indicates that the system p.f. and KVAR compensation are within set limits.
    No switching on or off can then take place.
9.  If 'O/V' L.E.D. glows and persists. it indicates that the system voltage has crossed safe value. The
    Controller trips all the stages and remains unaffected till supply voltage attains normal value.

TEST MODE OF OPERATION
    To avoid unnecessary switching of capacitors in this mode. keep 'Auto/Man' switch on the panel in
    'Man' position. When the push-button on the front panel marked "'TEST" is depressed inwards. the
    TEST mode is activated and input current signal connected at M & L terminals is internally
     disconnected. As such the PFCR cannot sense system P.F., and simulated current signal having
     typical power factor of 0.89 is internally injected, which is indicated in the digital p.f. display window.
     User can then have calibration check of the Controller as under ;

  COS Ø  Setting
   Adjust % KVAR setting=o
   if COS
Ø setting >0.89 the red LED marked (-) glows.
   i
f COS Ø setting <0.89 the amber LED marked (+) glows.

  % KVAR Setting
  Adjust COS
Ø setting = 1.0
  If % KVAR setting > 15% the green LED marked glows.
  If % KVAR setting < 15% the red LED marked (-) glows.
  Adjust COS
Ø setting = 0.8
  If % KVAR > 7% the green LED masked  glows
  If % KVAR < 7% the amber LED marked (+) glows.
  Note : Above values correspond to rated supply voltage.

  Next 

Home | Products | Profile | Instructions | Enquiry

Designed & Hosted by : MID   Promoted by : GID